Differential pressure regulator for precise control and optimization of the air pressure
The differential pressure regulator is used to measure small differential pressures of non-corrosive gases,
particularly air.
In addition to the measurement mode, the differential pressure regulator also features a control mode
Application
The device is used, for example, in air-conditioning systems, for controlling fans,
monitoring room pressure or controlling filters.
Setting options
The differential pressure controller can be switched between the metric and imperial systems of measurement.
Two setpoints can be set in the unit and selected via the dry contact input. The PI algorithm
calculates the measured differential pressure against the setpoint and controls the output signal so that a constant pressure response is achieved in accordance with the
setpoint. The output signal is available as a 0–10 V signal.
Special feature
In addition to differential pressure, flow rate can also be used for measurement and control.
|
Artikel-Nr. |
Messbereich |
|---|---|
|
63008 |
0 - 500 Pa |
|
63009 |
0 - 1000 Pa |
|
63010 |
0 - 4000 Pa |
|
63011 |
0 - 50 Pa |
|
63012 |
0 - 100 Pa |
Note: The device depends on its position, so it is important that it is mounted vertically.
Accessories
A ring test lead is required for testing the fan!
Please order this separately if required!
Item No. 63030:
(Mounting kit for ring measuring line for differential pressure regulator)
Includes 2 connection fittings, 2 m of 4 x 1.5 mm hose and 4 fixing screws
| operating mode | Measurement mode or control mode |
|---|---|
| Schutzart | IP54 according to EN 60529 |
| Umgebungstemperatur | -10°C … +50°C |
| EMC | CE mark, EN, EN50082-2, Inspection according to EN 50081-2 |
| Maße | 90x70x54mm |
| Messbereich | depending on the variant |
| Versorgungsspannung | 10-30 VDC / 24VAC |
| output voltage | can be set for control from 0.0V to 10.0V |